Fire extinguisher types and classes, with maintenance and test intervals

Updated September 5, 2026 · 6 min read · Standards cited: NFPA 10 (2022/2026 ed.), OSHA 29 CFR 1910.157

Fire extinguishers are rated by the class of fire they put out: A (ordinary combustibles), B (flammable liquids and gases), C (energized electrical), D (combustible metals), and K (cooking oils and fats). The most common workplace unit is a multipurpose ABC dry chemical extinguisher, which is hydrostatically tested every 12 years and internally examined every 6; CO2, water, and wet chemical Class K units are tested every 5 years.

The five fire classes

ClassFuelTypical agentWhere you find them
AWood, paper, cloth, trash, plasticsWater, foam, multipurpose dry chemicalOffices, warehouses, corridors
BGasoline, oil, grease, solvents, propaneDry chemical, CO2, clean agent, foamShops, fuel storage, loading docks
CEnergized electrical equipmentDry chemical, CO2, clean agentServer rooms, electrical rooms, labs
DMagnesium, titanium, sodium, lithiumDry powder (sodium chloride, copper)Machine shops, metal fabrication, labs
KCooking oils and animal fatsWet chemical (potassium acetate)Commercial kitchens

A single unit can carry several ratings; the red ABC dry chemical extinguisher covers the three most common classes and is the default in most commercial buildings.

Common extinguisher types and their intervals

TypeAgentSix-year internal examHydrostatic test
Multipurpose dry chemical (ABC), stored pressureMonoammonium phosphateYes, every 6 years12 years
Regular dry chemical (BC), stored pressureSodium bicarbonateYes, every 6 years12 years
Dry chemical, cartridge-operatedVariousAnnual (opened each year)12 years
Carbon dioxide (BC)CO2Not applicable5 years
Water, stored pressure (A)Water or antifreezeNot applicable5 years
Foam (AFFF, FFFP)Foam solutionNot applicable5 years
Wet chemical (K)Potassium acetateNot applicable5 years
Clean agent (Halotron, FE-36)HalocarbonYes, every 6 years12 years
Dry powder (D)Sodium chloride, copperYes, every 6 years12 years
Water mistDe-ionized waterNot applicable5 years

All types require the same monthly visual inspection (by trained staff) and annual maintenance (by a person certified under NFPA 10 §7.3). The six-year and hydrostatic intervals above apply to common types; confirm against the manufacturer's manual and the NFPA 10 edition your jurisdiction adopted.

Numerical ratings

Class A and B extinguishers carry numbers before the letter, for example 4A:80B:C. The Class A number is roughly equivalent to that many 1.25-gallon buckets of water; the Class B number is the square footage of flammable liquid fire a trained operator can extinguish. NFPA 10 sets minimum ratings by hazard level: for ordinary (light) hazard, a minimum 2-A rating with 75 ft travel distance; for extra (high) hazard, 4-A and 80-B with reduced travel distances.

Placement rules by class

  • Class A: within 75 ft of travel from any point; minimum 2-A for light hazard, 2-A for ordinary hazard (with 3,000 sq ft per unit of A), 4-A for extra hazard.
  • Class B: within 30 ft (5-B light, 10-B ordinary, 40-B extra) or 50 ft (10-B light, 20-B ordinary, 80-B extra).
  • Class C: placed according to the A or B hazard in the same area.
  • Class D: within 75 ft of the metal hazard.
  • Class K: within 30 ft of the cooking appliance; a placard must instruct users to activate the hood suppression system first.

Choosing and recording type in your inventory

Record the type and size for each unit in your inspection system, because the six-year and hydrostatic intervals depend on it. A common audit finding is a facility that tracks monthly inspections perfectly but has CO2 units eight years past hydrotest because every unit was assumed to be on the 12-year cycle.

Frequently asked questions

Can I use an ABC extinguisher on a kitchen grease fire?

Not as the primary protection. Commercial cooking with vegetable or animal oils requires a Class K wet chemical extinguisher within 30 feet of the appliance. ABC dry chemical can splatter burning oil and does not saponify it.

What extinguisher is required for a lithium battery fire?

Lithium-ion battery fires are not Class D (that is for lithium metal). Current guidance is large volumes of water or specialized lithium-ion agents; consult your fire protection company and the battery manufacturer. NFPA is developing further guidance.

How do I tell the hydrostatic test date?

It is stamped on the cylinder collar or shown on a label near the base as month and year, sometimes with the tester's mark. If the date plus the interval for that type is in the past, remove the unit from service.