Requirements

NFPA 10 inspection, maintenance, and testing requirements

Updated September 5, 2026 · 9 min read · Standards cited: NFPA 10 (2022/2026 ed.), OSHA 29 CFR 1910.157

NFPA 10 requires portable fire extinguishers to be visually inspected at intervals not exceeding 31 days (§7.2), maintained annually by a certified person (§7.3), internally examined every 6 years if stored-pressure dry chemical (§7.3.3), and hydrostatically tested every 5 or 12 years depending on type (Chapter 8). Each inspection must be recorded with month, year, and inspector initials on a tag or in an electronic record (§7.2.4).

What NFPA 10 is

NFPA 10, Standard for Portable Fire Extinguishers, is the National Fire Protection Association's consensus standard covering selection, placement, inspection, maintenance, and testing of portable extinguishers. It is not itself law, but it is adopted by reference in the International Fire Code and NFPA 1, which most U.S. jurisdictions enforce, and OSHA's 1910.157 tracks it closely. The current editions in use are 2022 and 2026; check which your jurisdiction has adopted.

Chapter 7.2: Inspection

Frequency. At installation and at intervals not exceeding 31 days (§7.2.1.2). More often where hazards, tampering, obstruction, or environment warrant (§7.2.1.1).

Procedure (§7.2.2). Confirm the extinguisher is in its designated location; that access and visibility are unobstructed; that operating instructions face outward and are legible; that the pressure gauge or indicator is in the operable range; that fullness is confirmed by weighing or hefting for units without gauges; that there is no obvious physical damage, corrosion, leakage, or clogged nozzle; that the pull pin and tamper seal are intact; and, for wheeled units, that the wheels, carriage, hose, and nozzle are in condition.

Corrective action (§7.2.3). Any deficiency found during inspection requires the extinguisher to be subjected to maintenance procedures (i.e., removed from service and handled by a certified technician).

Records (§7.2.4). Record the month and year the inspection was performed and the initials of the person performing it. The record may be kept on a tag or label attached to the extinguisher, on an inspection checklist kept on file, or by electronic method (§7.2.4.2). Records must be retained for 12 months (§7.2.4.4). Section numbering varies slightly between editions; the requirement does not.

Chapter 7.3: Maintenance

Annual maintenance (§7.3.1). At intervals not exceeding one year, or when an inspection reveals a deficiency, a certified person performs a thorough examination of the mechanical parts, extinguishing agent, expelling means, and physical condition, following the manufacturer's service manual. A maintenance tag or label with the date and the servicing agency is attached.

Six-year maintenance (§7.3.3). Stored-pressure dry chemical and halogenated agent extinguishers requiring a 12-year hydrostatic test must be emptied and subjected to the applicable internal and external maintenance procedures every 6 years. A six-year label is applied.

Certification. Maintenance must be performed by a "certified person" holding a certificate issued by an organization acceptable to the Authority Having Jurisdiction, typically the extinguisher manufacturer or a state fire equipment licensing program.

Chapter 8: Hydrostatic testing

Extinguisher typeTest interval
Stored-pressure water, water mist, loaded stream, antifreeze5 years
Wetting agent, AFFF, FFFP foam5 years
Carbon dioxide5 years
Wet chemical (Class K)5 years
Dry chemical, stored-pressure with mild steel or aluminum shells12 years
Dry chemical, cartridge- or cylinder-operated12 years
Halogenated agents, clean agents12 years
Dry powder (Class D), stored-pressure or cartridge12 years

Cylinders that show corrosion, damage, or repairs are condemned rather than tested. A hydrostatic test label or stamp records the month and year and the tester.

Chapter 6: Placement and mounting (the parts inspectors check)

  • Travel distance to an extinguisher: 75 ft for Class A; 30 ft (low rating) or 50 ft (high rating) for Class B; 30 ft for Class K from the cooking appliance; 75 ft for Class D.
  • Mounting height: extinguishers weighing 40 lb or less have the top no more than 5 ft above the floor; heavier units, no more than 3.5 ft. The bottom must be at least 4 in above the floor.
  • Extinguishers must be conspicuously located, and where visual obstruction cannot be avoided, signs or other means must indicate the location.
  • Cabinets must not be locked except where extinguishers are subject to malicious use, and then a means of emergency access must be provided.

Record-keeping summary

RecordContentRetention
Monthly inspectionMonth, year, inspector initials12 months
Annual maintenanceDate, servicing agency, technicianLife of extinguisher or 12 months past next maintenance
Six-year maintenanceDate, agencyUntil next six-year service
Hydrostatic testMonth, year, test pressure, testerUntil next test

A single system that holds all four records per extinguisher is the practical way to keep them straight across dozens of units, and to see at a glance where a record is missing. That is what FireGuard is.

Frequently asked questions

Is NFPA 10 a law?

Not by itself. It becomes enforceable when adopted by a jurisdiction, usually through the International Fire Code or NFPA 1, or when referenced by OSHA. Nearly every U.S. state enforces some edition of NFPA 10.

What edition of NFPA 10 applies to me?

The edition adopted by your state or local fire code, which often lags the newest edition by several years. Ask your fire marshal. The 2022 and 2026 editions have identical monthly inspection requirements for practical purposes.

Does NFPA 10 allow electronic inspection records?

Yes. §7.2.4.2 permits records to be kept by electronic method that provides a permanent record. Many jurisdictions still expect the physical tag to be marked as well.