Requirements

How often do fire extinguishers need to be inspected?

Updated September 5, 2026 · 5 min read · Standards cited: NFPA 10 (2022/2026 ed.), OSHA 29 CFR 1910.157

Fire extinguishers must be visually inspected at least once a month (NFPA 10 §7.2 says at intervals not exceeding 31 days; OSHA 1910.157(e)(2) says monthly), receive annual maintenance from a person certified under NFPA 10 (your fire protection contractor), have an internal examination every 6 years (stored-pressure dry chemical), and pass a hydrostatic test every 5 years (CO2, water, wet chemical) or 12 years (dry chemical). The monthly check can be done by your own trained staff. Which intervals apply depends on the extinguisher type and the NFPA 10 edition your jurisdiction adopted.

The four intervals at a glance

IntervalRequirementPerformed bySource
MonthlyVisual inspectionTrained employeeNFPA 10 §7.2; OSHA 1910.157(e)(2)
Every 12 monthsMaintenance examinationCertified person (NFPA 10 §7.3)NFPA 10 §7.3; OSHA 1910.157(e)(3)
Every 6 yearsInternal examination (stored-pressure dry chemical)Certified personNFPA 10 §7.3.3
Every 5 yearsHydrostatic test (CO2, water, foam, wet chemical)Certified personNFPA 10 Ch. 8; OSHA 1910.157(f)
Every 12 yearsHydrostatic test (dry chemical, halogenated)Certified personNFPA 10 Ch. 8; OSHA 1910.157(f)

Monthly: the one you own

The monthly inspection is a quick visual check: right place, accessible, gauge in the green, pin and seal intact, no damage, tag current. NFPA 10 phrases it as "at intervals not exceeding 31 days," which is why most facilities pick a fixed day each month. There is no requirement that it be done by a contractor. See the full monthly checklist.

Note the clock: the next inspection is due 30 days after the last one. If you inspected on the 3rd, the 31-day window closes on the 3rd or 4th of next month, not "sometime in the month."

Annual: the one you schedule

Once every 12 months, a person certified under NFPA 10 §7.3 (in practice, a fire protection contractor; some states also license this work) performs a thorough maintenance examination: mechanical parts, extinguishing agent, expelling means, and physical condition. They attach a new service tag with the date. OSHA 1910.157(e)(3) requires the employer to "assure that portable fire extinguishers are subjected to an annual maintenance check" and to record the annual maintenance date and keep that record for one year after the last entry or the life of the shell, whichever is less. Federal OSHA does not itself say who must perform the check; NFPA 10 and state rules do.

Six-year: the one everyone forgets

Stored-pressure dry chemical extinguishers (the common red ABC units) must be emptied and internally examined every 6 years. The technician applies a six-year label. If your tag shows the last six-year service and it was more than 72 months ago, the unit is out of compliance even if the annual tags are current.

Hydrostatic: the one that depends on type

The cylinder itself is pressure-tested on a cycle set by construction and agent: every 5 years for carbon dioxide, water, foam, and wet chemical units; every 12 years for dry chemical and clean-agent units. The date is stamped or labeled on the cylinder. A unit past its hydrotest date must be removed from service.

When inspections are required more often

NFPA 10 §7.2.1.1 calls for more frequent inspection when any of these apply: high frequency of fires in the past, severe hazards, locations that make units susceptible to mechanical damage or tampering, exposure to abnormal temperatures or corrosive atmospheres, or a history of the units being blocked or obstructed. Many warehouses and outdoor installations move to weekly checks for these reasons.

What "electronic monitoring" changes

Recent editions of NFPA 10 recognize electronic monitoring as an alternative to some manual monthly checks when a monitoring system continuously supervises the extinguisher's presence, pressure, and obstruction and reports to a constantly attended location. Very few facilities have such sensor systems, and whether the provision applies depends on the edition your jurisdiction adopted. Scanning a QR code and recording a check in software is not electronic monitoring; the monthly walk remains required, and a digital record of that walk is simply the modern form of the tag.

Frequently asked questions

Is the monthly inspection required by law or only by NFPA?

Both. OSHA 29 CFR 1910.157(e)(2) is federal law for general industry workplaces and requires monthly visual inspection. NFPA 10 is the consensus standard adopted by most state and local fire codes, and it sets the same interval along with the detail of what to check.

What happens if I miss a month?

Perform the inspection as soon as you notice and document the gap honestly. A single late inspection is a correctable deficiency; a pattern of missing months, or no records at all, is what draws an OSHA citation (maximum $16,550 per serious violation under the 2025 penalty schedule).

How often must extinguishers be replaced?

Extinguishers are not replaced on a fixed schedule; they are maintained and tested. Disposable (non-rechargeable) units are typically replaced after 12 years. Any unit that fails maintenance or a hydrostatic test is removed and replaced.